Product Specifications (In-Rack 300kW CDU) | |
Cooling Capacity | 192kW at 5°C approach 301kW at 7°C approach |
Power Consumption | 2,000W (Typ) 3,400W (Max) |
Fluid Temp. Range | 15°C to 70°C |
Flow Rate | 288 LPM (Typ) 400 LPM (Max) |

SmartSense CDU
Modular Coolant Distribution Unit

Product Specification (six-module configuration) | |
Cooling Capacity | 1.2 MW at 6°C approach 1.8 MW at 9°C approach |
Power Consumption | 30.6 kW |
Available Pumping Pressure | 1,200 LPM at 35 psid |
Module Cluster Control | Primary-Secondary |

Modular Coolant Distribution Unit
Interested in Row-Based or L2A CDUs?
Vertically Integrated Racks with Flex
- Global manufacturing, services and support
- End-to-end data center solutions across power, cooling and IT
- Custom, configurable data center racks delivered at scale
Contact Our Team to Learn More
Explore JetCool's Other Products

Liquid-Cooled Dell XE7745 Server
JetCool’s solutions for the platform integrates direct-to-chip liquid cooling delivering up to 30% server power savings over air-cooled configurations.

SmartPlate System for Dell PowerEdge Servers
- Save an average of 13% on server power savings overnight
- Supports 1,500W in 2U configurations
- Maximize compute per floor tile and minimize facility floorspace with no piping or plumbing

Liquid-Cooled Racks
Backed by 100+ thermal experts, we engineer each system for maximum performance, efficiency, and scalability. With global manufacturing, commissioning, and lifecycle support, JetCool delivers end-to-end rack infrastructure built to scale with your business.

SmartLid: Liquid-to-Die Cooling
- Optimize OPEX by balancing free cooling with evaporative cooling in most climates
- Future-proof system design with the capacity to cool the next three generations of processors, including those that exceed 1,000W per chip